HXGN15-12 HV Switchgear Metal-clad AC Ring Main Unit

XGN15-12 HV switchgear metal enclosed AC ring main unit is a new HV apparatus which introduced from abroad and accord with the requirement of rural distribution and city distribution in nation.

Email to Us

Overview


HXGN15-15 switchgear is suitable for power systems with an AC frequency of 50Hz and a voltage of 12kV. It is widely used in industrial and residential cable ring networks and power supply terminals.

It is particularly suitable for the following locations: small secondary substations, switch stations, urban residential area distribution, industrial and mining enterprises, shopping malls, airports, subways, wind power plants, hospitals, stadiums, and railways.

 

Operating Conditions


1. Ambient temperature: -35℃ ~+45℃;

2. Altitude: 1000m;

3. Relative humidity: daily average 95%, monthly average 90%;

4. Seismic resistance: 8 magnitude.

5. Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration, without strong shake.

Technical Specification


Item Unit Parameter
Rated voltage kV 12
Rated frequency Hz 50
Main busbar rated current A 630/125
Main loop, earthing loop rated short time withstand current kA/s 20/3
Main loop, earthing loop rated peak withstand current kA 50
Main loop, earthing loop rated short circuit making current kA 50
Load break switch full capacity breaking time Times 100
Fuse breaking current kA 31.5
Rated loop breaking current A 630
Rated transfer current A 870
Mechanlcal life Times 2000
1min P.F. Withstand (virtral value), phase to phase, earth / across open contacts kV 42/48
Lightning impulse withstand voltage (peak) phase to phase, earth / across open contacts kV 75/85
Secondary loop 1min P.F. Withstand kV 2
Protection degree IP3X
EnglishEnglish